AK-30 Three-Phase Relay Test Equipment

AK-30 Three-Phase Relay Test Equipment

AC voltage source with 4 channels, current source and aux with 6 channels. DC source can be used simultaneously

Amplitude, frequency and phase angle can be adjusted respectively, independently and continuously; Control via PC via Ethernet RJ45 interface

DSP and FPGA technology integrated with our own patent for high performance amplifier technology

Able to analyze all types of relays (current, voltage, frequency, power, impedance, harmonics, distance, ...)

Able to have the advanced function of GPS triggering, Oscillation, Frequency Protection. Repeat Transcient with comtrade file; IEC61850 solution (optional).

Full self-protection & alarm indicators for incorrect connection, open circuit, short circuit, overload & overheating, etc.

Test modules including the AK family catalogue:

  • AC & DC test
  • Ramping Test
  • Overcurrent Test
  • State Sequence
  • Distance Protection
  • Differential Rate Protection
  • Reclose test
  • Synchronizer test
  • Fault Recurrence (COMTRADE Transient Analysis)
  • Time Characteristic

Special modules (optional):

  • Power Swing
  • Frequency Test
  • Standard Meter - Multi-function meter (Optional)
  • Recorder - Transient Recorder (Optional)
  • Energy Meter Calibration (Optional)
  • Transmitter Calibration (Optional)

AK30 Series Relay Test Equipment

  • AK3030: 3x30A / 4x130V
  • AK3063: 3x40A, 6x20A / 4x130V
  • AK3063+: 3x60A, 6x30A / 4x130V
  • AK3066: 3x40A, 6x20A / 7x130V
  • AK3066+: 3x60A , 6x30A / 7x130V
  • AK3030i: 3x30A/ 4x300V
  • AK3063i: 3x60A , 6x30A / 4x300V
  • AK3066i: 3x60A, 6x30A / 7x300V

Technical data:

Voltage Source

Ranges

4-phase CA(L-N)

4x0...300V

2-phase AC (L-L)

2x0...600V

Power

4-phase CA (L-N)

4x110VA, at 0...300V

2-phase AC (L-L)

2x220VA, at 0...600V

Accuracy

<0.14% reading + 0.06% guaranteed range at 0...300V <0.04% reading + 0.01% typical range at 0...300V

Resolution

1 mV

Current Source

Ranges

6-phase CA (L-N)

6x0...30A

3-phase CA (L-N)

3x0...60A

1-phase CA (L-N)

1x0...180A

Power

6-phase CA (L-N)

1x450 VA, at 0...30A

3-phase CA (L-N)

1x600 VA, at 0...60A

1-phase CA (L-N)

1x1000 VA, at 0...180A

Accuracy

<0.14% reading + 0.06% guaranteed range at 0...30A <0.05% reading + 0.02% typical range at 0...30A

Resolution

1 mA

Binary Data Entries

Number

8 Pairs

Compatible voltage

10V...250V/2A

Binary Data Output

Number

4 Pairs

Capacity

250V/3A

Synchronization

Synchronization mode

GPS

Capacity

250V/3A

Harmonics

Order

2 … 20

Generator, general

Frequency

Range

0...1000 Hz

Accuracy

<0.001 Hz to 10...450 Hz<0.
01 Hz to 450...1000 Hz

Resolution

0.001 Hz

Phase

Range

-360º ... +360º

Accuracy

< 0.2º

Resolution

0.1º

Weather

Range

0…9999.999s

Accuracy

1 ms

DC generator

Voltage Range

0...300V / 180 W

Current Range

0...20A / 300 W

Accuracy

<0.14%lect + 0.06%r.g (0-20A)

<0.05%lect + 0.02%r.t (0-20A)

Resolution

1mA; 1mV

DC Aux Source

Range

0...300V / 0.6 A

Food

Nominal voltage

220 V±20% Vac

Power

1000 VA

Nominal frequency

50/60 Hz±10%.

Environmental conditions

Operating temperature

-5ºC...55ºC

Storage temperature

-20ºC...75ºC

Moisture range

≤90%, no condensation

Others

Weight

24 kg (act. to 17.5 kg)

Dimensions

360x460x140 (mm)

PC connection

RJ45

Download the catalogue of AK-30 Three-Phase Relay Test Equipment.

If you want to acquire Relay testing with quality, you can also consult prices of Relay testing.

If you have any doubts or need advice from our engineers, don't hesitate to contact us and we will be pleased to help you. You can also call us at (+34) 982 20 99 20.