info@amperis.com (+34) 982 20 99 20
AMIC-5000 tester is designed to measure insulation resistance of power cables, transformers, motors and other electrically powered devices. Additionally the device allows for measurement of AC and DC voltages. Input circuits of the measuring devices are electronically protected from overloading, e.g. due to incorrect connection to the circuit being tested or incorrect use of input terminals.
Insulation resistance measurement
AC/DC voltage measurement |
||
Range |
Resolution |
Accuracy |
0...600V |
1V |
±(3%m.v. + 2 digits) |
50Hz (sinusoidal shape with harmonic contents < 2%) |
Leakage current reading |
||
Range |
Resolution |
Accuracy |
0...Ipmax |
depending on range RISO |
(-∆I- , +∆I+) |
Ipmax - maximum converter current 1,2 ± 0,2 mA |
||
(-∆I- , +∆I+) - current reading accuracy calculated using the following formula: |
||
∆I-= UISO.(1/R -1/(R+|∆R| )) |
||
UISO - test voltage |
Insulation resistance measurement
Range |
Resolution |
Accuracy |
0,0...999,9kΩ |
0,1kΩ |
±(3%.m.v. + 20 digits) |
1,000...9,999MΩ |
0,001MΩ |
|
10,0...99,99MΩ |
0,01MΩ |
|
100,0...999,9MΩ |
0,1MΩ |
|
1,000...9,999GΩ |
0,001GΩ |
|
10,0...99,99GΩ |
0,01GΩ |
|
100,0...999,9GΩ |
0,1GΩ |
|
1,000...5,000TΩ |
0,001TΩ |
|
For measurements of limited converter current, the accuracy is not specified |
||
Minimum insulation resistance measured without limited converter current: |
|
Voltage UISO |
Range |
250V |
250kΩ |
500V |
500kΩ |
1000V |
1,0MΩ |
2500V |
2,5MΩ |
5000V |
5,0MΩ |
“m.v.” = “measured value” |
Specifications AMIC-5000 |
|
Electric security: |
|
Type of insulation |
Double, acc. to EN 61010-1 and IEC 61557 |
Measurement category |
CAT III 600V EN 61010-1 |
Measurement category for terminals and circuit 5kV |
extrapolada III 5000V |
Protection class acc. to EN 60529 |
IP54 |
Rated operational conditions: |
|
Operating temperature |
-10...+50°C |
Test voltage accuracy (Robc[Ω] ≥1000*UN [V]) |
0 +10% of the set value |
Voltage fluctuation due to temperature changes - better than |
0,2% / ºC |
Converter output current |
min. 1,0mA for rated test voltag |
1,0...3,0mA for 2500V |
|
1,0...1,4mA for 5000V |
|
Measurement rate |
approx. 1 measure/second |
Quality standard |
ISO 9001 |
Other technical data: |
|
Power supply |
Juego de baterías Ni-MH |
Power supply adaptor |
100...240V |
tmín measurement 5kV/1mA acc. EN 61557 (5s/25s) |
5h or 600 measurements |
Time to auto-off |
300 sec. (mode RISO/IL: depends on T2 and T3 ; tOFF= T2/ T3 + 300sec.) |
Weight |
1,9kg |
Dimensions |
295 x 222 x 95 mm |
Display |
LCD |
Standard accesories:
Optional accesories: